Reference PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 156 of 228 ProSoft Technology, Inc.
May 14, 2014
(This table has been taken directly from the IEC 61850 Standard document)
ctlVal
This must be set for:
SPC (Single Point Control)
DPC (Double Point Control)
INC (Controllable Integer Status)
BSC (Binary Controlled Step Position Information)
ISC (Integer Controlled Step Position Information
CDCs (Common Data Classes)
(This table has been taken directly from the IEC 61850 Standard document)
setMag
This must be set by the user for APC (Controllable Analogue Set Point
Information) CDC.
operTm
The PLC user sends a command with operate time to the gateway, and the
gateway uses time activated control, e.g. it sends the time of operation to the
IED. The IED needs to support the time activated control.
origin.orCat
The orCat could have these values. The value depends upon the role of the
PLC. E.g. if the PLC is a station control, then this value will never change.
not-supported
orCat is not supported
bay-control
Control operation issued from an operator using a Client located at bay level
station-control
Control operation issued from an operator using a Client located at station
level
remote-control
Control operation from a remote operater outside the substation (for example
network control center)
automatic-bay
Control operation issued from an automatic function at bay level
automatic-station
Control operation issued from an automatic function at station level
automatic-remote
Control operation issued from a automatic function outside of the substation
maintenance
Control operation issued from a maintenance/service tool