QTS-CLX-PVX Page 17
2. Use the Actions/Start Auto Configuration menu command or use Auto
Configuration toolbar command to start an auto-configuration cycle.
WARNING!
Resetting the PROVOX controller disrupts the running system!
Reset the controller only at a time when it is safe to do so.
3. Reset the PROVOX master. The QTS-CLX-PVX captures the configuration
data the master sends out and passes it to the configuration program, which
analyzes it and builds the tree.
4. Download the captured configuration to the QTS-CLX-PVX.
5. Export aliases from the configuration tool to a file.
6. Import those aliases into RSLogix 5000.
7. Use the aliases to monitor data on the PROVOX bus.
If the module does not capture the configuration within a timeout period (approximately
60 seconds), it displays this message.