DFNT ProLinx Gateway Diagnostics and Troubleshooting
EtherNet/IP Explicit Messaging Client/Server Protocol Manual
ProSoft Technology, Inc. Page 67 of 124
July 24, 2013
4.6.4 PCCC Response Errors
Error (Int)
Error (Hex)
Description
-81
0xFFAF
Message Length received not valid
-82
0xFFAE
Command code returned not valid
-83
0xFFAD
Session handle field invalid
-84
0xFFAC
Status error reported
-85
0xFFAB
Context field not matched
-86
0xFFAA
CPF item count not correct
-87
0xFFA9
CPF address field error
-88
0xFFA8
CPF packet tag invalid
-89
0xFFA7
CPF bad command code
-90
0xFFA6
CPF invalid IOI
-91
0xFFA5
CPF status error reported
-92
0xFFA4
-93
0xFFA3
TSN in PCCC message not matched
-94
0xFFA2
CPF not correct message number
-95
0xFFA1
CPF incorrect connection ID value returned
-96
0xFFA0
Incorrect session handle returned
Vedere la pagina 66