Reference IEC-101 Slave ProLinx Communication Gateway
Protocol Manual IEC 60870-5-101 v3 Slave (Firmware version 3.xx)
Page 92 of 159 ProSoft Technology, Inc.
August 6, 2010
Refer to the following parameter to configure the select/operate timeout period.
After the gateway receives the SELECT operation it will wait for this period of
time for the EXECUTE operation. If the gateway does not receive an EXECUTE
operation within this period of time it will require another SELECT operation
before the EXECUTE operation.