Prosoft-technology MVI56E-MNETCR Manuale Utente Pagina 31

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 30
MVI56E-MNETCR ♦ ControlLogix Platform Start Here
Modbus TCP/IP Multi Client Enhanced Communications Module for Remote Chassis User Manual
ProSoft Technology, Inc. Page 31 of 159
June 14, 2011
Create the Module - Local Rack
1 In the C
ONTROLLER
O
RGANIZATION
window, expand the I/O configuration
node.
2 Select the 1756
B
ACKPLANE
node, and then click the right mouse button to
open a shortcut menu. On the shortcut menu, choose N
EW
M
ODULE
...
3 This action opens the S
ELECT
M
ODULE
dialog box.
4 Select the 1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click OK.
5 Set the Module Properties values as follows:
Parameter Value
Name Enter a module identification string. The recommended value is
MNETCR.
Description Enter a description for the module. Example: Modbus TCP/IP
Multi Client Enhanced Communications Module for Remote
Chassis.
Comm Format
Select D
ATA
-INT
(Very Important)
Slot Enter the slot number in the rack where the MVI56E-MNETCR
module is to be installed.
Input Assembly Instance 1
Input Size 42
Output Assembly Instance 2
Output Size 42
Configuration Assembly Instance 4
Configuration Size 0
Vedere la pagina 30