MVI69-DNPSNET ♦ CompactLogix or MicroLogix Platform Ladder Logic
Distributed Network Protocol Interface Module
Page 38 of 119 ProSoft Technology, Inc.
November 3, 2008
Each of these object types are discussed in the following topics:
DNPSlvStat
This object holds the module status information transferred with each read data
block transferred from the module. The structure of the object is shown in the
following example:
Name Data Type Description
Scan_Cnt INT Program Scan Counter
Product_Name SINT[4] Product Code
Rev_Level SINT[4] Revision
Op_Sys SINT[4] Operating system revision
Run_Number SINT[4] Run number
Blk_Rd_Count INT Number of block read transfers
Blk_Wr_Count INT Number of block write transfers
Blk_Parse_Cnt INT Number of blocks parsed by module
Blk_Err INT Number of block errors
Rx_Frames INT Number of frames received for this unit
Tx_Frames INT Number of frames transmitted for this unit
Rx_Total INT Number of frames received
Sync_err INT Sync error count
Overrun_err INT Overrun error count
len_err INT Length error count
CRC_err INT CRC error count
Overflow_err INT Overflow error count
Seq_err INT Sequence error count
Addrs_err INT Address error count
BI_Events INT Number of binary events generated
BI_Queue INT Number of binary events in queue
AI_Events INT Number of analog input events
AI_Queue INT Number of analog input events in queue
FL_Queue INT Float Input Event Count in Buffer
Reserved INT Reserved
Bad_func_err INT Number of bad function code error count
Ukn_Obj_err INT Unknown Object error count
Range_err INT Range error count
App_Overflow INT Number of application level overflow errors
Multi_Frame_err INT Multi-frame error count
UDP_Rx_Count INT UDP Recieve Count
UDP_Tx_Count INT UDP transmit Count
Unsol_error INT Unsolicited Error Count
State_Value INT State Value
TCP_ST_value INT TCP Socket State Value
Commenti su questo manuale