Example Configurations PLX8x-MNET-61850 Communication Gateway
User Manual Modbus TCP/IP to IEC 61850
Page 64 of 228 ProSoft Technology, Inc.
May 14, 2014
3.1.2 Configuring the ProSoft Gateway
Before any MMS messages are mapped, the ProSoft Gateway must be
configured so that the IP address will be in the same subnet as the GE Multilin
relay device.
1 Right click on the ProSoft Gateway icon.
Choose PROPERTIES and another ProSoft Gateway Configuration window will
open.
This configuration window is for the ProSoft Gateway device itself. On this
window you can set the IP address, change the project name, set the SNTP
server, and setup Modbus address mapping. The PLX Read Start and PLX Write
Start are used to set the ProSoft gateway's beginning Modbus register
addresses. This allows other Modbus Client devices to access the ProSoft
gateways internal memory database through the gateway’s Modbus TCP/IP
server.