Prosoft-technology MVI69L-MBS Manuale Utente Pagina 146

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 154
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 145
Reference MVI69L-MBS CompactLogix Platform
User Manual Communication Module
Page 146 of 154 ProSoft Technology, Inc.
January 6, 2014
RS-232: Null Modem Connection (Hardware Handshaking)
This type of connection is used when the device connected to the module
requires hardware handshaking (control and monitoring of modem signal lines).
RS-232: Null Modem Connection (No Hardware Handshaking)
This type of connection can be used to connect the module to a computer or field
device communication port.
Note: For most null modem connections where hardware handshaking is not required, the Use
CTS Line parameter should be set to N and no jumper will be required between Pins 7 (RTS) and 8
(CTS) on the connector. If the port is configured with the Use CTS Line set to Y, then a jumper is
required between the RTS and the CTS lines on the port connection.
Vedere la pagina 145

Commenti su questo manuale

Nessun commento