Diagnostics and Troubleshooting MVI69L-MBS CompactLogix Platform
User Manual Communication Module
Page 94 of 154 ProSoft Technology, Inc.
January 6, 2014
3 In the Diagnostics window, click the SET UP CONNECTION button.
4 In the Connection Setup dialog box, click the BROWSE DEVICE(S) button to
open the ProSoft Discovery Service. Select the module, then right-click and
choose ASSIGN TEMPORARY IP.
5 The module’s default IP address is usually 192.168.0.250. Choose an unused
IP within your subnet, and then click OK.
Important: The temporary IP address is only valid until the next time the module is initialized. For
information on how to set the module’s permanent IP address, see Ethernet 1 on page 59.