MVI69L-MBS ♦ CompactLogix Platform MVI69L-MBS Configuration
Communication Module User Manual
ProSoft Technology, Inc. Page 55 of 154
January 6, 2014
Additional Configuration Parameters as a Slave
Sets the number of milliseconds to wait before responding to
a command received on the port from a remote Master. This
delay is sometimes required to accommodate slower Master
devices.
Defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed
by the module. Verify that each device has a unique address
on a network.
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 2
commands. For example, if the value is set to 150, an
address request of 0 returns the value at register 150 in the
database.
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 4
commands. For example, if the value is set to 350, an
address request of 0 returns the value at register 350 in the
database.
Specifies the offset address into the internal Modbus
database for network requests for Modbus function 1, 5 or 15
commands. For example, if the value is set to 100, an
address request of 0 corresponds to register 100 in the
database.
Specifies the offset address in the internal Modbus database
for network requests for Modbus function 3, 6, or 16
commands. For example, if a value of 250 is entered, a
request for address 0 corresponds to the register 250 in the
database.