Prosoft-technology MVI69L-MBS Manuale Utente Pagina 33

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 154
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 32
MVI69L-MBS CompactLogix Platform Connecting to RSLogix 5000
Communication Module User Manual
ProSoft Technology, Inc. Page 33 of 154
January 6, 2014
2 Set the Module Properties values as follows:
Parameter
Value
Name
Enter a module identification string. Example: MVI69LMBS
Description
Enter a description for the module. Example: ProSoft
communication module for Serial Modbus communications.
Comm Format
Select Data-INT
Slot
Enter the slot number in the rack where the MV69E-MBS
module is installed.
Input Assembly Instance
101
Input Size
242
Output Assembly Instance
100
Output Size
241
Configuration Assembly Instance
102
Configuration Size
0
This module must be configured with a block transfer size of 240 words (input
block size = 242 words, output block size = 241 words):